Grid Power & PFC

AC Real, Reactive & Apparent Power

SYSTEM TYPE

Voltage (V_rms)V
Current (I_rms)A
Power Factor (PF)cos(θ)

PFC (POWER FACTOR CORRECTION)

Target Power Factor
FrequencyHz
Real (W) Reactive (VAR) Apparent (VA) θ
Real Power (P)
0 kW
Reactive (Q)
0 kVAR
Apparent (S)
0 kVA
Correction Required
Reactive Power to compensate:
0 kVAR
Capacitance (each delta branch for 3φ):
0 μF

Math & Theory

Sinusoidal steady-state, lagging displacement power factor only; three-phase assumes a balanced load and line-to-line RMS voltage. S = VI (single phase) or √3 VLL IL; P = S·PF, Q = S√(1−PF²). Correction Qc = P[tan(acos(PF))−tan(acos(target))]. Capacitance is per delta branch for three phase, or the single capacitor for one phase. Harmonics, resonances, switching and capacitor ratings require separate analysis.